Title 13 WATER AND SEWERS
Chapter 13.12 SERVICE DESIGN REQUIREMENTS*
13.12.010 Chapter application.
13.12.020 Psi defined.
13.12.030 Principles of design.
13.12.040 Total requirements for water flow.
13.12.050 Average required daily water flow, OD.
13.12.060 Duration of average daily required domestic water flow.
13.12.070 Required fire flow and duration.
13.12.080 Alternate systems.
13.12.090 Pressures.
13.12.100 Storage.
13.12.110 Computation of source capacity.
13.12.120 Bacterial quality of water.
13.12.130 Chemical quality of water.
* For statutory provisions regulating water quality control, see Water Code
§ 13000 et seq.
13.12.010 Chapter application.
In applying the minimum requirements found in this chapter for design and
construction of a water system, consideration shall be given to the quantity of
water pumped and stored, the adequacy and dependability of all waterworks
facilities, the physical conditions known to exist at the time and place of
installation, and the probable operating requirements. (Ord. 383 § 125,
1974).
13.12.020 Psi defined.
As used in this chapter the letters “psi” mean pressure in
pounds per square inch gauge. (Ord. 383 § 126, 1974).
13.12.030 Principles of design.
All facilities shall be of adequate size and capacity and shall be
correlated with source facilities and storage facilities to meet the
requirements of Section 13.12.040. All facilities shall be designed structurally
to withstand the physical stresses to which they shall be subjected and shall be
free from structural and sanitary hazards. (Ord. 383 § 127,
1974).
13.12.040 Total requirements for water flow.
A. The total required water flow for any given service area under
consideration or unit water system, except for small water systems, shall be the
sum of the minimum fire flow plus the maximum daily domestic water flow
requirements. The maximum daily water flow requirements shall be either two, two
and one-half, or three and one-half times the average daily water flow
requirements depending upon whether the water system is to be metered, unmetered
without yard irrigation, or unmetered with yard irrigation.
OT
equals OF plus 2 OD for metered service;
OT
equals OF plus 2.5 OD for unmetered without yard
irrigation;
OT equals OF plus 3.5 OD for
unmetered with yard irrigation.
Where: OT equals the total
required water flow, OF equals the minimum required fire water flow
(see Section 13.12.070), and OD equals the average daily required
water flow (see Section 13.12.050). All flows are to be expressed in gallons per
minute.
B. Small Water Systems.
1. For small water systems serving four
or less residential units, the minimum required water flow shall be two and
two-tenths gallons per minute for each unit, if the well has been pump tested
according to county standards. A well driller’s yield test may be
accepted, but the total required water flow shall be three and three-tenths
gallons per minute for each unit for the required flow.
2. The distribution
system shall be capable of delivering the required domestic flow for a minimum
duration of two hours. A storage tank shall be provided to augment a well supply
to furnish the required water flow.
3. The system shall have a
hydropneumatic tank to provide a minimum pressure of twenty-five psi in the
water system, if necessary. The pressure tank shall have a minimum capacity of
two hundred gallons.
4. A variance may be granted by the board of
supervisors, after notice and hearing, to the provisions of this subsection
pertaining to small water systems. The order granting such variance shall set
forth the reasons for the granting of such variance. (Ord. 383B, 1978: Ord. 383
§ 140, 1974).
13.12.050 Average required daily water flow, OD.
The average required daily water flow in gallons per minute for domestic
or developed area used in the water system shall be obtained by the following
formula: OD equals two and one-half times SU times DF, in
gallons per minute; where OD equals the average daily required
water flow for domestic use, SU equals the number of service units which reflect
type and number of water services, and DF equals the density factor. The average
daily required flow in gallon per minute in the water system for commercial,
industrial, irrigation and other uses shall be described in detail and supported
with data.
Supporting data shall be submitted with all water system
improvement plans and shall be subject to the review and approval of the county
engineer.
The county engineer shall be guided by, but may adjust the
quantities set forth in the following subsections of local
condition:
Service Units (SU).
1. Residential: Each single-family
dwelling or lot will be counted at the rate of 0.35 service units per capita
with a minimum of three capita per lot. Each family dwelling unit of duplex or
triplex status, or a mobilehome, shall be counted at the rate of 0.6 service
units per family unit. Each family dwelling unit of an apartment building shall
be counted at the rate of 0.5 service units per family unit.
2. Commercial,
Industrial, Agricultural: Service units are to be based upon actual conditions.
Each acre will be counted as a minimum of five service units.
B. Density
Factor (DF).
The density factor takes into account the number of service
connections involved within any system or section thereof and reflects density
and probability. The following density factors are established by this
article:
DF equals 2.00 for systems with 5 service connections or
less
DF equals 1.60 for systems with 20 service connections
DF equals
0.90 for systems with 40 service connections
DF equals 0.70 for systems with
80 service connections
DF equals 0.60 for systems with 100 service
connections
DF equals 0.45 for systems with 200 service
connections
Values for DF between the numbers of service connections listed
shall be determined by interpolation. (Ord. 383 § 141, 1974).
13.12.060 Duration of average daily required domestic water flow.
The distribution system shall be capable of delivering the average daily
required domestic water flow for a minimum duration of two hours. (Ord. 383
§ 142, 1974).
13.12.070 Required fire flow and duration.
The water system for all structures shall meet the requirements set forth
in Appendix III-A of the California Fire Code. Those areas not served by a
public water system shall comply with Section 1142 of the National Fire Codes of
the National Fire Protection Association (NFPA 1142). The following types of
structures shall be exempt from the above requirements:
A. Buildings within
an agricultural zoning district in which at least fifty percent of the total
floor space, whether enclosed by walls or not, is used for the storage of farm
equipment and supplies;
B. One- and two-family dwellings, if and only if
those structures are located within five miles’ driving distance from a
water tender or maintain an insurance services office rating (ISO) of
“Rural 8” or better. Any one- or two-family dwelling located more
than five miles’ driving distance from a water tender or not maintaining
an ISO of Rural 8 or better shall store a minimum of two thousand five hundred
gallons of water onsite at all times. (Ord. 598 § 2, 2004: Ord. 542
§ 2, 1991: Ord. 383A § 1, 1978: Ord. 383 § 143,
1974).
13.12.080 Alternate systems.
In lieu of the fire flow requirements of Section 13.12.070 the county
engineer may approve a fire plan for industrial developments utilizing other
fire suppression methods. Such plans may use automatic chemical suppression
systems in combination with a reduced fire flow from the water system. (Ord.
383 § 144, 1974).
13.12.090 Pressures.
The distribution system shall be of adequate size and so designed in
conjunction with related facilities to maintain normal operating pressures of
not less than thirty psi nor more than one hundred psi at the service
connection, except that during the periods of maximum hourly demand the
pressures shall not be less than twenty-five psi nor more than one hundred and
twenty-five psi. The computations for fire flow shall be based upon a minimum
of twenty psi residual operating pressure at the hydrant. Water pressures may
be greater than one hundred and twenty-five psi if the operator notifies the
customer in writing. (Ord. 383 § 160, 1974).
13.12.100 Storage.
Storage capacity shall be provided in new subdivisions to protect the
users from failure of domestic supply and to assure an adequate quantity of
water for fire protection in the event of a power or source failure or major
disruption of the distribution system. Storage shall be an elevated tank or
reservoir such as to provide gravity flow to the point of demand or, an
additional power supply or standby power may be used as an alternate. A
maintenance plan for standby power systems shall be submitted to the county
engineer for approval. Underground storage and storage in pipelines will not be
taken into consideration in meeting minimum storage requirements. Storage shall
be determined by the following criteria:
|
TYPE OF WATER SUPPLY
|
PERCENTAGE OF DAILY DOMESTIC USE COMBINED WITH FIRE FLOW
REQUIREMENT
|
|
A. Single power source, no standby power and a single source of
supply
|
50
|
|
B. Single power source, with standby power and a single source of
supply
|
25
|
|
C. Double power source, single source of supply
|
10
|
|
D. Multiple power source, multiple source of supply
|
0
|
(Ord. 383 § 161, 1974).
13.12.110 Computation of source capacity.
The engineer for the developer shall file with the county engineer a
computation of the water supply requirements for a subdivision or development to
be served by a water utility. (Ord. 383 § 162, 1974).
13.12.120 Bacterial quality of water.
Water as drawn from wells and springs and treated water sources, shall
meet the U.S. Public Health Service “Drinking Water Standards” as to
bacteriological quality. Water from untreated surface sources shall meet water
quality standards as established by the county health department. (Ord. 383
§ 170, 1974).
13.12.130 Chemical quality of water.
The chemical constituents should not occur in excess of the concentrations
recommended by the U.S. Public Health Service standards where other more
suitable supplies are available in the judgment of the county health department.
In addition to the above chemical standards, the taste, odor and appearance of
the water should be such that it is generally acceptable to the consumers.
(Ord. 383 § 171, 1974).
<< previous | next >>