Title 13 WATER AND SEWERS
Chapter 13.30 STANDARDS--PIPE FITTINGS
13.30.010 Certificate.
13.30.020 Cast iron bell and spigot fittings.
13.30.030 Cast iron flanged fittings.
13.30.040 Steel pipe fittings.
13.30.050 Asbestos-cement pipe fittings.
13.30.010 Certificate.
The supplier shall furnish a certificate if requested by the county
engineer, for those items for which a certificate is requested. The certificate
shall state that all pipe, valves, fittings, tanks, and protective coatings
comply with the specifications in this article. (Ord. 383 § 260,
1974).
13.30.020 Cast iron bell and spigot fittings.
All cast iron bell and spigot fittings shall conform to either AWWA
C100-55 (Standard, Class D, 173 psi), or AWWA C110-52 (Short-Body, 3 inch to 12
inch, 250 psi). Class D or class 150 is the minimum class acceptable. All cast
iron fittings installed below ground shall be lined and coated in accordance
with Section 13.18.030. (Ord. 383 § 261, 1974).
13.30.030 Cast iron flanged fittings.
All cast iron pipe flanged fittings shall conform to ASA B16. 4-1949, and
be lined and coated in accordance with Section 13.18.030. (Ord. 383 § 262,
1974).
13.30.040 Steel pipe fittings.
All steel pipe fittings shall have a minimum well thickness not less than
the steel pipe specified. Dimensions of the fittings shall conform to AWWA
C208-59. All steel fittings installed below ground shall be protected in the
manner as the pipe to which they are attached. (Ord. 383 § 263,
1974).
13.30.050 Asbestos-cement pipe fittings.
All asbestos-cement water pipe fittings shall comply with AWWA C400-64T.
(Ord. 383 § 264, 1974).
<< previous | next >>