Title 13 WATER AND SEWERS
Chapter 13.42 STANDARDS--PREPARATION FOR USE
13.42.010 Pressure test.
13.42.020 Leakage test.
13.42.030 Fire flow tests.
13.42.040 Disinfecting.
13.42.010 Pressure test.
New or repaired water distribution mains shall be tested to a minimum
hydrostatic pressure of fifty psi greater than the design pressure for the
system or pipe class. Class 150 pipe shall be tested to a minimum pressure of
two hundred psi. The duration of the test shall be one hour. All water mains
with cement joints shall not be tested until thirty-six hours after the joint
was made. All asbestos-cement pipe shall be filled with water for at least
twenty-four hours before testing. Before applying the hydrostatic pressure, all
entrapped air shall be thoroughly bled off. (Ord. 383 § 325,
1974).
13.42.020 Leakage test.
For all types of water mains, there shall be no visible leakage at any
point or section of pipe and the allowable leakage for the total lengths of all
water main under tests shall not exceed the amount specified in following
formula, L = ND (P)1/2 /3, 700, where L is the allowable
leakage in gallons per hour, D is the nominal diameter of the pipe in inches, P
is the test pressure during the leakage test and N is the number of joints in
the length of pipeline being tested. (Ord. 383 § 326, 1974).
13.42.030 Fire flow tests.
Tests shall be made by flowing fire hydrants of all new water distribution
systems.
All tests shall be made in the presence of the county engineer or
an authorized representative and no joint, valve, fitting or connection shall be
completely covered until inspected and approved. (Ord. 383 § 327,
1974).
13.42.040 Disinfecting.
All new or repaired mains, pumps, tanks, wells and other facilities for
handling potable water, before being placed in service, shall be completely
disinfected in accordance with “Procedures for Disinfecting Water
Mains,” AWWA C601-54. Every new water main and every repaired section of
an existing water main must be given an application of chlorine between fifty to
one hundred parts per million of chlorine in potable water. The new or repaired
pipe and/or facility shall be thoroughly flushed before and after chlorination.
If the first application of chlorine is not sufficient, the procedure shall be
repeated until the water will meet the bacteriological drinking water standards
as set forth in the United States Public Health Service “Drinking Water
Standards.” Any other disinfecting procedure, if approved by the county
health officer, may be used. (Ord. 383 § 328, 1974).
<< previous | next >>